🎨 Visualization Controls
Temperature Range
Tmin (°C)
Tmax (°C)
Thermal Palette
Opacity
100%
ASHRAE Compliance
ASHRAE Class
🏭 Facility Specifications
Overview of the currently loaded digital twin model.
📊 Compare Scenarios
AAU Data Center - Baseline vs Retrofitted Design KPIs (CFD and field-measured Experimental results).
KPI Baseline Retrofitted (CFD) Enhancement (CFD) Retrofitted (Experimental) Enhancement (Experimental)
RCIHI 205.80 215.80 -4.85% 106.80 +56.97%
RCILO 174.20 164.20 +5.74% 118.80 +33.53%
RTI 46.11 80.55 +74.69% 96.80 +52.07%
RHI 0.78 0.92 +17.94% 92.67% +34.53%
RI 97.21 99.57 +2.42% 97.88 +21.36%
🌿 Sustainability Impact
Thermal limit analysis & carbon optimisation
⚡ OPTIMIZATION MODE
System operating below ASHRAE limit
🌡️ Thermal Analysis
Max Rack Surface Temp
ASHRAE Limit (T_limit) 32.0 °C
Thermal Margin / Exceedance
Safety Margin
Usable / Required ΔT
💡 RECOMMENDED ACTION
⚙️ Parameters
Safety MarginBuffer below/above limit
°C
CO₂ FactorGrid emission intensity
kgCO₂/kWh
COPCooling coefficient of performance
⚡ Power Breakdown
IT Load — kW
Cooling Power (current) — kW
Cooling Power (optimised) — kW
Total (current) — kW
Total (optimised) — kW
📊 Key Metrics
PUE (current)
Power Usage Effectiveness
PUE (optimised)
Power Usage Effectiveness
CO₂ Emissions (current) — kgCO₂/h
CO₂ Emissions (optimised) — kgCO₂/h
Annual CO₂ Saving
🔧 Retrofit Recommendations
Note: Retrofit analysis is based on CFD airflow observations. CO₂ savings for retrofit measures cannot be quantified without additional simulation data.
📊 Scenario Summary
Performance metrics and KPI assessment for the active scenario.
🔥
Max Rack Surface Temp
--
💨
Avg Airflow
--
KPI Performance Indicators
KPI Value Assessment
RCIHI -- 🔥 Hot-air recirculation
RCILO -- ❄️ Cold-air bypass
RTI -- ⚠️ Overcooling
RHI -- 🔥 Moderate hot-air recirculation
RI -- 🔥 Hot-air recirculation
CCI -- ⚠️ Overcooling and inefficient airflow
T [°C]
-- -- --
32 27 18
X
Y
Z
Lx: -- m
Ly: -- m
Lz: -- m
📊
No Data Loaded
Load a VTK/VTM file to visualize thermal data
Loading...
Energy efficiency enhancement in two European data centers through CFD modeling
Abstract
The new reporting scheme adopted by the European Union focuses on the efficiency assessment of data centers based on key performance indicators (KPIs). This has the potential to lead to further measures for improving energy efficiency of data centers. Consequently, a systematic approach is crucial for assessing and improving data center performance. This study investigates efficiency assessment of two European pilot data centers, located in Denmark and Poland, according to the KPIs calculated through Computational Fluid Dynamics (CFD) simulations of airflow and thermal structures. Two separate experimental approaches were adopted at the pilot sites. One measured airflow and temperatures using external sensors at server inlets and outlets, while the other measured inlet temperatures from embedded server sensors. The good agreement observed between simulated and experimental data confirmed the accuracy of the computational model. The validated CFD model was applied to investigate efficiency improvement opportunities by retrofitting the thermal environment such as rack positioning, containment implementation, and guided airflow control. A series of numerical simulations are performed using the validated numerical model and KPIs are calculated for each design. Numerical simulations demonstrate that the efficiency of an existing data center can be enhanced by up to 75% using the presented approach, although the improvement varied significantly with the specific KPIs. The computational approach proposed here can be readily generalized to guide the efficiency assessment and improvement of existing data centers.
Flow chart for the KPI-informed enhancement approach: Numerical Model, Validation, Calculate Efficiency Metrics, Strategy, Improvable decision loop, Retrofitted Design
Flow chart for the KPI-informed enhancement approach.
Access the full paper here →
AAU Retrofitted Design - Experimental Data
Field validation of the KPI-informed retrofit at the AAU pilot data center (Aalborg University, Denmark).
Approach
The CFD-based study identified promising retrofit strategies, but numerically optimized designs are not always fully implementable on site. In this follow-up field study, the CFD-recommended actions were physically installed at AAU and validated with real measurements (server inlet/outlet temperatures, airflow velocities, rack-level power) under four IT load levels (25%, 50%, 75%, 100%), so both thermal and energy KPIs could be compared directly against the baseline under real operating conditions.
AAU BUILD facility, server racks, and ceiling-mounted fan coil unit
AAU BUILD facility - the six-rack, two-fan-coil pilot data center used for the field trial.
Separator wall and filler plates installed as part of the AAU retrofit
Implemented retrofit hardware: the hot/cold aisle separator wall (left) and filler plates sealing unused rack slots (right).
Tested Configurations
ConfigurationWhat was done
BaselineOriginal condition, no modifications
PlateFiller plates installed to close unused/inactive server openings, reducing cold air leakage
WallSeparating wall only, to isolate hot exhaust air from the supplied cold air
Plate+WallFiller plates combined with the separator wall - local sealing plus room-level airflow separation
Average KPIs by Configuration
Averaged across all four tested IT load levels (25-100%).
TestPIT (kW)PDC (kW)RCIHIRCILORTIRHI (%)RIPUECoP
Baseline0.662.11248.2178.7202.0068.8880.653.240.45
Plate0.972.14200.5212.690.4971.5485.052.230.81
Wall0.891.83159.6143.499.9882.3490.902.290.77
Plate+Wall0.901.96106.8118.896.8092.6797.882.180.84
Enhancement--56.97%33.53%52.07%34.53%21.36%32.71%86.66%
AAU average thermal and energy KPI comparison across Baseline, Plate, Wall and Plate+Wall configurations, with the ideal value shown as a dashed line
Figure 4 - Average thermal/energy KPIs across all four field-tested AAU configurations vs the ideal value (dashed line). Plate+Wall (red) sits closest to ideal across nearly every KPI.
Results
All three retrofit configurations improved on the baseline, but through different mechanisms. The Plate Test alone reduced RTI sharply (202.02 → 90.49) by closing unused server openings, but RCILO actually worsened (178.7 → 212.6), showing local sealing alone doesn't give the most balanced rack inlet temperatures. Plate+Wall gave the best overall result: RCIHI, RCILO, RHI and RI all improved the most, PUE dropped from 3.24 to 2.18 and CoP rose from 0.45 to 0.84 - a 32.7% energy efficiency improvement. Applied to a representative 300 kW small-scale data center, this translates to roughly 2.07 GWh/year in energy savings, about €0.38M/year in cost savings, and about 382 tCO₂e/year in avoided emissions.
PSNC Retrofitted Design - Experimental Data
Field validation of the KPI-informed retrofit at the PSNC pilot data center (Poznan Supercomputing and Networking Center, Poland).
Approach
PSNC is a micro-data center with two rack cabinets in an open-aisle layout, cooled by ceiling-mounted air conditioners. Unlike AAU, only one retrofitted configuration was field-tested here (not four), because several CFD-recommended actions - notably a thermal separator - could not be installed due to practical and safety constraints. The implemented actions were: rack rotation and repositioning, closing/minimizing ventilation grills, removing one server unit and non-essential furniture, and running the supply air at a controlled 18°C. The results below should be read as a partially implemented retrofit, not the fully CFD-optimized design.
PSNC building exterior and server rack cabinet
PSNC facility - the two-rack, HVAC and ventilation pilot data center used for the field trial.
Annotated photo showing closed ventilation grills, rack inlets, and AC supply/return grills at PSNC
Implemented retrofit hardware: closed ventilation grills, rack inlets, and AC supply/return grills, as installed at PSNC.
Baseline vs Retrofitted (Experimental)
Enhancement (%) is not printed directly in the source report's table for PSNC (unlike AAU's Table 5) - calculated here the same way the source paper computes its own CFD Enhancement figures (% change in the improving direction per KPI).
KPIIdealBaselineRetrofittedEnhancement
RCIHI100301.27288.19+4.34%
RCILO10064.5586.34+33.76%
RTI100275.20107.76+60.84%
RHI-32.0047.00+46.88%
RI10069.5275.26+8.26%
Results
The largest improvement was in RTI, which dropped from 275.20 to 107.76 - a substantial reduction in cold air bypass and much better balance between supplied cooling air and heat removed from the IT equipment. RCILO improved from 64.55 to 86.34, showing more effective cold air delivery to rack inlets, and RHI rose from 32.00 to 47.00, showing better use of the supplied cold air - though still below the ≥80 target, so heat capture wasn't fully optimized. RI improved only moderately (69.52 → 75.26) and RCIHI barely moved (301.27 → 288.19), staying far from the ideal value of 100. This is consistent with the thermal separator - the measure CFD identified as most impactful - not being implemented here. In short: the feasible field actions clearly helped, but full CFD-recommended airflow separation (as achieved at AAU) would likely be needed to fully resolve recirculation and localized hotspot risk at PSNC.
CFD vs. Experimental
Interestingly, the original CFD-optimized design (see "Retrofitted → CFD") actually predicted RCIHI and RCILO getting worse (-18.67% and -54.76%) under the fully separated design, likely a side effect of concentrating airflow more tightly once the thermal separator is in place. The field-measured partial retrofit shows the opposite for those two KPIs (+4.34% and +33.76%) - a reminder that the two results represent different designs (full CFD-optimized vs. partially field-implemented) and are not directly comparable one-to-one. Both approaches agree that RTI, RHI, and RI all improve.
Contact Us
Get in touch to learn more.